Summary

A number of compromise incidents involving remote supervision devices in cooling systems have occurred in France, as reported by CERT-FR via alert CERTFR-2026-ALE-012. The affected devices include the Danfoss AK-SM/AK-SC series and Copeland/Dixell XWEB. There are six relevant vulnerabilities across these two product groups that could potentially allow unauthorized access, information disclosure, configuration manipulation, remote command execution, and operational disruptions.

Affected Products

  • Danfoss AK-SM/AK-SC series (specifically Danfoss AK-SM 8xxA)
  • Copeland/Dixell XWEB (specifically Copeland XWEB Pro)

Technical Details

Six identified vulnerabilities affect these two product groups:

  • Danfoss AK-SM 8xxA:

    • CVE-2025-41450: Authentication bypass and sensitive information disclosure.
    • CVE-2025-41451: OS command injection potentially allowing post-authentication remote command execution.
    • CVE-2025-41452: Web interface configuration manipulation that can lead to Denial of Service (DoS).
  • Copeland XWEB Pro:

    • CVE-2026-21718: Authentication bypass potentially enabling pre-authentication code execution.
    • CVE-2026-24663: OS command injection enabling unauthenticated remote code execution.
    • CVE-2026-25085: Authentication bypass allowing unauthorized access.

Impact

Exploitation of these vulnerabilities could potentially result in:

  • Unauthorized system access.
  • Sensitive information disclosure.
  • Unauthorized configuration changes.
  • Disruption of cooling system monitoring and control.
  • Impact on operational continuity and potential economic losses.

Mitigation

  • Disable direct internet management access, implement VPNs, strong authentication, OT network segmentation, and firewall access restrictions.
  • Perform firmware updates for confirmed vulnerable Danfoss AK-SM 8xxA and Copeland XWEB Pro devices according to vendor recommendations, backed by configuration backups and device functional testing.
  • Check for indicators of compromise (IoC), secure digital evidence, isolate high-risk access, and perform system recovery while maintaining operational continuity.
  • Strengthen OT device inventory management, monitor vendor support status, and plan for the replacement of End of Life (EOL) devices.

References

  • CERT-FR (CERTFR-2026-ALE-012)
  • Security Advisory: Kerentanan Pada Sistem Pendingin Danfoss dan Copeland